Heat to Power: Thermal Energy Harvesting and Recycling for Warm Water-Cooled Datacenters
Xinhui Zhu, Weixiang Jiang, Fangming Liu, Qixia Zhang, Li Pan, Qiong Chen, Ziyang Jia
摘要
Warm water cooling has been regarded as a promising method to improve the energy efficiency of water-cooled datacenters. In warm water-cooling systems, hot spots occur as a common problem where the hybrid cooling architecture integrating thermoelectric coolers (TECs) emerges as a new remedy. Equipped with this architecture, the inlet water temperature can be raised higher, which provides more opportunities for heat recycling. However, currently, the heat absorbed from the server components is ejected directly into the water without being recycled, which leads to energy wasting. In order to further improve the energy efficiency, we propose Heat to Power (H2P), an economical and energy-recycling warm water cooling architecture, where thermoelectric generators (TEGs) harvest thermal energy from the “used” warm water and generate electricity for reusing in datacenters. Specifically, we propose some efficient optimization methods, including an economical water circulation design, fine-grained adjustments of the cooling setting and dynamic workload scheduling for increasing the power generated by TEGs. We evaluate H2P based on a real hardware prototype and cluster traces from Google and Alibaba. Experiment results show that TEGs equipped with our optimization methods can averagely generate 4.349 W, 4.203 W, and 3.979 W (4.177 W averagely) electricity on one CPU under the drastic, irregular and common workload traces, respectively. The power reusing efficiency (PRE) can reach 12.8% 16.2% (14.23% averagely) and the total cost of ownership (TCO) of datacenters can be reduced by up to 0.57%.
问问这篇 Paper
智能体会读完全文。
Lune 把这篇 Paper 索引到了每一个公式,引用它的顶会 Paper 也一样。你提问,回答直接引用原文。
引用它的顶会 Paper1
问问它们各自怎么用它相关 Paper
- Soil-Monitoring Sensor Powered by Temperature Difference between Air and Shallow Underground SoilNatsuki Ikeda, Ryo Shigeta, Junichiro Shiomi, Yoshihiro KawaharaUbiComp 2020 · 被引用 39 次
- Data Center Cooling System Optimization Using Offline Reinforcement LearningXianyuan Zhan, Xiangyu Zhu, Peng Cheng, Xiao Hu 等ICLR 2025
- UPTPU: Improving Energy Efficiency of a Tensor Processing Unit through Underutilization Based Power-GatingPramesh Pandey, Noel Daniel Gundi, Koushik Chakraborty, Sanghamitra RoyDAC 2021 · 被引用 10 次
- Cost-Efficient Overclocking in Immersion-Cooled DatacentersMajid Jalili, Ioannis Manousakis, Iñigo Goiri, Pulkit A. Misra 等ISCA 2021 · 被引用 54 次
- AgileWatts: An Energy-Efficient CPU Core Idle-State Architecture for Latency-Sensitive Server ApplicationsJawad Haj-Yahya, Haris Volos, Davide B. Bartolini, Georgia Antoniou 等MICRO 2022 · 被引用 22 次